Bucharest, Romania Data Center

This data center provides a strategic location in Eastern Europe with robust connectivity, skilled talent, EU compliance, energy sustainability, and political stability.

Summit c/o NXDATA-1 Bucharest Data Center (BUH1)
8 Dimitrie Pompeiu Boulevard, 3rd Floor, Feper Building
Sector 2, 020337, Bucharest, Romania

Bucharest Romania data center

Technical Specifications

These are the nuts and bolts.

Power

  • Total IT Power: 2+ MW across 2,500 m² of technical space, with over 4,000 interconnected circuits
  • UPS: 2N redundancy with a capacity of 2 x 800 kVA, 2 x 400 kVA, 2 x 300 kW and 2 x 400 kW respectively, and a 15-minute battery runtime
  • Generators: Fully rated N+N diesel generators with a total capacity of 2 x 1,500 kVA, 2 x 802 kVA and 4 x 571 kVA, and 12-hour fuel autonomy at full load and continuous-run capability
  • Connection: Two 2,000 kVA/20 kV MV/LV transformers connect to the national power grid

Cooling

  • Adiabatic cooling system with a N+1 redundancy configuration, keeping temperatures of 22°C ± 3°C and a humidity range of 50% ± 20%

Network

  • Direct access to the Netcity metropolitan network (from East to West)
  • Fiber optic network access in Metrorex tunnels, Pipera metro station, Iride business park, and Conect business park in Pipera platform
  • Internet Exchange access (INTERLAN-IX and RONIX) through NXDATA-1
  • Balkan-IX and BalkanIX through the NXDATA-1 / NXDATA-2 fiber ring

Security

  • Video Surveillance System: Continuous monitoring of access paths and colocated equipment with footage roll-back period of 30 days
  • 24×7×365 operating service

Facility

Get to know the lay of the land.

Fire Detection & Suppression

  • Detection: VESDA (Very Early Smoke Detection Apparatus), as well as a classic detection system that includes smoke, temperature, pressure, and humidity sensors
  • Suppression system: INERGEN cylinders and inert gas at 300 bar pressure

Airports

  • Bucharest Henri Coandă International Airport (OTP) 9 miles (14.4km)

Parking

  • On-site parking

Building

  • Building Structure: 5 Story
  • Total Building Size: 26,900 ft²
  • Total Space: 5,500 m² (approx. 59,200 ft²)
  • White Space: 2,000 m² across 4 data halls (500 m² / ~5,380 ft² each)
  • Seismic Safety: Seismic base-isolation system under all data hall floors
  • Floor Load Capacity: 20 kN/m²

Perks

Welcome to the good life, where the amenities are as solid as our uptime.

Support

  • Service Desk Support 24/7
  • Remote Hands

Compliance

  • ISO 27001 (Information Security)
  • ISO 9001 (Quality Management)
  • Built to Tier III design targets

Service Level Agreements

  • 99.999% SLA for electricity supply and climate control
  • 100% uptime SLA on network and power

Amenities

  • Managed loading dock
  • Customer cages
  • Custom-built suites
  • Staging & storage areas
  • Dedicated workspace
  • Cafeteria

The proof is in the praise

With the volume of data we manage, a migration was not going to be a trivial effort. Summit made a compelling case to move our primary hosting to take advantage of their network, expertise, and support, rather than purchasing a point-to-point product from a traditional carrier and paying for cross-connects on each side. This was a critical component that set the stage for the larger migration.